Tankless Water Heater Size Calculator

Size simultaneous GPM and heat input so the coldest incoming water still gets hot, then screen the candidate unit's published rating.

Inputs

Fixtures that can run at the same time

The worst case, not the daily average. Two showers plus a sink is the usual whole-home design point.

Showerheads made after 1 Jan 1994 are capped at 2.5 gpm at 80 psi (10 CFR 430.32(p)).

Lavatory and kitchen faucets at the same time.

Faucets made after 1 Jan 1994 are capped at 2.2 gpm at 60 psi (10 CFR 430.32(o)).

A filling tub holds a large share of the simultaneous flow.

Tub fillers are not covered by the EPAct faucet limit, so read the actual rate; filler spouts commonly deliver 4-8 gpm.

Dishwasher fill, clothes washer fill, a hose bib or anything else that runs at the same moment. Leave 0 if nothing else runs.

Enter 0 to use the fixture total above. Use this when you already have a flow figure from a fixture-unit takeoff or from the manufacturer's worksheet.

Temperatures

This is the design case for tankless. Groundwater runs about 37-45 F in the northern states in winter, near 50 F in the mid-Atlantic and 65-75 F in the Deep South. Note that the 58 F used by the DOE UEF test procedure (10 CFR 430 Subpart B Appendix E 2.3) is a rating condition, not a cold-season design value.

Warm-season groundwater runs roughly 15-20 F warmer than winter, which is why a unit that keeps up in July can fail in January.

The fixture temperature you are designing to.

The unit you are considering

Decides whether the answer is read in amps or in MBH.

From the spec sheet: the gallons per minute the unit is published to deliver at its rated temperature rise. Leave 0 to skip the screen.

The rise the rated flow is quoted at - usually printed next to the GPM, for example '6.6 GPM at 35 F rise'.

The flow below which the burner does not fire. Typically 0.5-0.75 gpm; small draws such as a single lavatory can fall under it and get no hot water at all.

Result

Simultaneous flow to cover
—
Input required at cold-season rise
—
Electric input required
—
Electric current at 240 V
—
Gas input required
—
—
—
Fuel-specific checks
—
Where this stops applying
—
Rated unit delivers, warm season
—
Rated unit delivers, cold season
—
Input required at warm-season rise
—
Calculation details
Flow headroom against the cold-season case
—
Delivered / required flow
—
Showers
—
Sinks
—
Smallest single draw
—
Warm-season temperature rise
—
Tub fillers
—
Heat input implied by the published rating
—
Cold-season temperature rise
—

What to check

  • Fixtures that can run at the same time, with their flow rates
  • Cold-season and warm-season groundwater temperatures
  • The published GPM rating and the temperature rise it is quoted at
  • Gas meter and line capacity, or the electrical service capacity

Standards referenced

  • DOE Uniform Energy Factor test procedure — 10 CFR Part 430, Subpart B, Appendix E · Uniform test method for measuring energy consumption of water heaters; UEF ratings on nameplates and EnergyGuide labels come from this procedure.
  • DOE water conservation standards for faucets, showerheads and appliances — 10 CFR 430.32(f), (g), (o) and (p) · Maximum flow rates and water use for faucets (2.2 gpm at 60 psi), showerheads (2.5 gpm at 80 psi), dishwashers and clothes washers. These are the figures the fixture-flow defaults in the hot water demand and tankless sizing calculators reproduce.
  • National Fuel Gas Code (ANSI Z223.1 / NFPA 54) — Current edition · Gas piping sizing, appliance input limits and venting requirements for gas-fired water heaters. The calculators state the required input and direct the line sizing to this code rather than attempting it.
  • UL 1738 venting systems for gas-burning appliances, categories II, III and IV — Current edition · Listing requirements for the vent material used with condensing gas appliances. Tankless and condensing water heaters must use a vent system listed for the appliance category, which is why the calculators do not size venting.

Related calculators

Screening estimate only. The result panel lists the limits that apply to this calculation. Verify nameplate data, rates, groundwater temperatures and installer quotes before deciding, and have gas, venting and electrical installations checked against the local code by a licensed contractor.